Controller LonWorks®
750-819
Technical data
| Visualization | none |
| Programming languages per IEC 61131-3 | Instruction List (IL) Ladder Diagram (LD) Function Block Diagram (FBD) Continuous Function Chart (CFC) Structured Text (ST) Sequential Function Chart (SFC) |
| Programming environment | WAGO-I/O-PRO V2.3 (based on CODESYS V2.3) |
| Transmission rate | 0.078 Mbit/s |
| Bus segment length (max.) | 2700 m; 500 m (free topology); 2700 m (bus topology) |
| Transmission medium (communication/fieldbus) | Twisted pair – FTT |
| Topology | per LON specification |
| Number of fieldbus nodes on master (max.) | 127 |
| Program memory | 128 KB |
| Data memory | 64 KB |
| Non-volatile software memory | 7kbyte |
| Number of modules per node (max.) | 62 |
| Transceiver | FTT 10 A |
| Supply voltage (system) | 24 VDC (-15 … +20 %); via pluggable connector (CAGE CLAMP® connection) |
| Input current (typ.) at nominal load (24 V) | 500mA |
| Power supply efficiency (typ.) at nominal load (24 V) | 87% |
| Current consumption (5 V system supply) | 300mA |
| Total current (system supply) | 1,700mA |
| Supply voltage (field) | 24 VDC (-15 … +20 %); via power jumper contacts |
| Current carrying capacity (power jumper contacts) | 10A |
| Number of outgoing power jumper contacts | 3 |
| Isolation | 500 V system/field |
Connection data
| Connection technology: communication/fieldbus | LonWorks: 1 x Male connector; 2-pole |
| Connection technology: system supply | 2 x CAGE CLAMP® |
| Connection technology: field supply | 6 x CAGE CLAMP® |
| Connection type | System/field supply |
| Strip length | 8 … 9 mm / 0.31 … 0.35 inches |
| Connection technology: device configuration | 1 x Male connector; 4-pole |
Physical data
| Width | 50.5 mm / 1.988 inches |
| Height | 100 mm / 3.937 inches |
| Depth | 71.1 mm / 2.799 inches |
| Depth from upper-edge of DIN-rail | 63.9 mm / 2.516 inches |
Mechanical data
| Mounting type | DIN-35 rail |