750-553
Number of analog outputs | 4 |
Total number of channels (module) | 4 |
Signal type | Current |
Signal type (current) | 0 … 20 mADC |
Actuator connection | 4 x (2-wire) |
Resolution [bit] | 12Bit |
Data width | 4 x 16-bit data; 4 x 8-bit control/status (optional) |
Load impedance | Either 0 … 300 Ω or 300 … 600 Ω (same resistance for all load impedances) |
Conversion time (typ.) | 10ms |
Measurement error (reference temperature) | 25°C |
Measurement error, deviation (max.) from the upper-range value | 0.1% |
Temperature error (max.) of the upper-range value | 0.01%/K |
Output error, reference temperature | |
Output error, deviation (max.) of the upper-range value | 0.1% |
Temperature error (max.) of the output range value | 0.01%/K |
Recovery time (typ.) | 100ms |
Supply voltage (system) | 5 VDC; via data contacts |
Current consumption (5 V system supply) | 60mA |
Supply voltage (field) | 24 VDC (-25 … +30 %); via power jumper contacts (power supply via blade contact; transmission (supply voltage field side only) via spring contact) |
Isolation | 500 V system/field |
Indicators | LED (A) green: function; LED (B) red: Error |
Number of incoming power jumper contacts | 2 |
Number of outgoing power jumper contacts | 2 |
Connection technology: inputs/outputs | 8 x CAGE CLAMP® |
Connection type 1 | Inputs/Outputs |
Solid conductor | 0.08 … 2.5 mm² / 28 … 14 AWG |
Fine-stranded conductor | 0.08 … 2.5 mm² / 28 … 14 AWG |
Strip length | 8 … 9 mm / 0.31 … 0.35 inches |
Width | 12 mm / 0.472 inches |
Height | 100 mm / 3.937 inches |
Depth | 69.8 mm / 2.748 inches |
Depth from upper-edge of DIN-rail | 62.6 mm / 2.465 inches |
Mounting type | DIN-35 rail |
Color | light gray |
Housing material | Polycarbonate; polyamide 6.6 |
Fire load | 0.964MJ |
Weight | 50.5g |
Conformity marking | CE |
Ambient temperature (operation) | 0 … +55 °C |
Ambient temperature (storage) | -40 … +85 °C |
Protection type | IP20 |
Pollution degree | 2 per IEC 61131-2 |
Operating altitude | 0 … 2000 m / 0 … 6562 ft |
Mounting position | Horizontal left, horizontal right, horizontal up, horizontal down, vertical top and vertical bottom |
Relative humidity (without condensation) | 95% |
Vibration resistance | 4g per IEC 60068-2-6 |
Shock resistance | 15g per IEC 60068-2-27 |
EMC immunity to interference | per EN 61000-6-2, marine applications |
EMC emission of interference | per EN 61000-6-4, marine applications |
Exposure to pollutants | Per IEC 60068-2-42 and IEC 60068-2-43 |
Permissible H2S contaminant concentration at a relative humidity 75 % | 10ppm |
Permissible SO2 contaminant concentration at a relative humidity 75 % | 25ppm |