750-362
Communication | Modbus (TCP, UDP) |
ETHERNET protocols | HTTP(S) BootP DHCP DNS SNTP FTP(S) SNMP |
Baud rate | 10/100 Mbit/s |
Transmission medium | Twisted Pair S-UTP; 100 Ω; Cat. 5; 100 m maximum cable length |
Transmission performance | Class D per EN 50173 |
Number of modules per node (max.) | 250 |
Number of modules without a bus extension (max.) | 64 |
Input and output process image (fieldbus) max. | 1020 words/1020 words |
Supply voltage (system) | 24 VDC (-25 … +30 %); via pluggable connector |
Current consumption (5 V system supply) | 350mA |
Total current (system supply) | 700mA |
Input current (typ.) at nominal load (24 V) | 280mA |
Power supply efficiency (typ.) at nominal load (24 V) | 90% |
Isolation | 500 V system/field |
Indicators | LED (LINK/ACT) green: Network connection via ports 1 … 2; LED (MS, NS) red/green: Status of node, network; LED (I/O) red/green/orange: Status of local data bus |
Connection technology: communication/fieldbus | Modbus (TCP, UDP): 2 x RJ-45 |
Connection technology: system supply | 2 x CAGE CLAMP® |
Connection technology: device configuration | 1 x Male connector; 4-pole |
Connection type 1 | System supply |
Solid conductor | 0.08 … 2.5 mm² / 28 … 14 AWG |
Fine-stranded conductor | 0.08 … 2.5 mm² / 28 … 14 AWG |
Strip length | 8 … 9 mm / 0.31 … 0.35 inches |
Width | 49.5 mm / 1.949 inches |
Height | 96.8 mm / 3.811 inches |
Depth | 71.9 mm / 2.831 inches |
Depth from upper-edge of DIN-rail | 64.7 mm / 2.547 inches |
Mounting type | DIN-35 rail |
Housing material | Polycarbonate; polyamide 6.6 |
Fire load | 1.453MJ |
Weight | 104.8g |
Conformity marking | CE |
Ambient temperature (operation) | 0 … +55 °C |
Ambient temperature (storage) | -25 … +85 °C |
Protection type | IP20 |
Pollution degree | 2 per IEC 61131-2 |
Operating altitude | 0 … 2000 m / 0 … 6562 ft |
Mounting position | Horizontal left, horizontal right, horizontal up, horizontal down, vertical top and vertical bottom |
Relative humidity (without condensation) | 95% |
Vibration resistance | 4g per IEC 60068-2-6 |
Shock resistance | 15g per IEC 60068-2-27 |
EMC immunity to interference | per EN 61000-6-2, marine applications |
EMC emission of interference | per EN 61000-6-3, marine applications |
Exposure to pollutants | Per IEC 60068-2-42 and IEC 60068-2-43 |
Permissible H2S contaminant concentration at a relative humidity 75 % | 10ppm |
Permissible SO2 contaminant concentration at a relative humidity 75 % | 25ppm |