Electrical data
Ratings per IEC/EN
Ratings per UL
Ratings per CSA
Ex information
Reference hazardous areas | See application instructions in section “Knowledge and Downloads – Documentation – Additional Information: Technical Section; Technical Explications” |
Ratings per | ATEX: PTB 03 ATEX 1162 U / IECEx: PTB 03.0004U (Ex eb IIC Gb) |
Rated voltage EN (Ex e II) | 550V |
Rated current (Ex e II) | 22A |
Rated current (Ex e II) with jumper | 20A |
Power Loss
Power loss, per pole (potential) | 0.766W |
Rated current IN for specified power loss | 24A |
Resistance value for specified, current-dependent power loss | 0.001Ω |
Connection data
Connection points | 3 |
Total number of potentials | 1 |
Number of levels | 1 |
Number of jumper slots | 2 |
Connection 1
Connection technology | Push-in CAGE CLAMP® |
Actuation type | Operating tool |
Connectable conductor materials | Copper |
Nominal cross-section | 2.5 mm² |
Solid conductor | 0.25 … 4 mm² / 22 … 12 AWG |
Solid conductor; push-in termination | 0.75 … 4 mm² / 18 … 12 AWG |
Fine-stranded conductor | 0.25 … 4 mm² / 22 … 12 AWG |
Fine-stranded conductor; with insulated ferrule | 0.25 … 2.5 mm² / 22 … 14 AWG |
Fine-stranded conductor; with ferrule; push-in termination | 1 … 2.5 mm² / 18 … 14 AWG |
Note (conductor cross-section) | Depending on the conductor characteristic, a conductor with a smaller cross-section can also be inserted via push-in termination. |
Strip length | 10 … 12 mm / 0.39 … 0.47 inches |
Wiring direction | Front-entry wiring |
Physical data
Width | 5.2 mm / 0.205 inches |
Height | 59.2 mm / 2.33 inches |
Depth from upper-edge of DIN-rail | 32.9 mm / 1.295 inches |
Mechanical data
2002-1301
Mounting type | DIN-35 rail |
Marking level | Center/side marking |
Material data
2002-1301
Color | gray |
Material group | I |
Insulation material | Polyamide (PA66) |
Flammability class per UL94 | V0 |
Fire load | 0.147MJ |
Weight | 6.1g |