5/5 - (2 bình chọn)
2002-1201
Connection data
| Clamping units | 2 |
| Total number of potentials | 1 |
| Number of levels | 1 |
| Number of jumper slots | 2 |
Connection 1
| Connection technology | Push-in CAGE CLAMP® |
| Actuation type | Operating tool |
| Connectable conductor materials | Copper |
| Nominal cross-section | 2.5 mm² |
| Solid conductor | 0.25 … 4 mm² / 22 … 12 AWG |
| Solid conductor; push-in termination | 1 … 4 mm² / 18 … 12 AWG |
| Fine-stranded conductor | 0.25 … 4 mm² / 22 … 12 AWG |
| Fine-stranded conductor; with insulated ferrule | 0.25 … 2.5 mm² / 22 … 14 AWG |
| Fine-stranded conductor; with ferrule; push-in termination | 1 … 2.5 mm² / 18 … 14 AWG |
| Note (conductor cross-section) | Depending on the conductor characteristic, a conductor with a smaller cross-section can also be inserted via push-in termination. |
| Strip length | 10 … 12 mm / 0.39 … 0.47 inches |
| Wiring direction | Front-entry wiring |
Physical data
| Width | 5.2 mm / 0.205 inches |
| Height | 48.5 mm / 1.909 inches |
| Depth from upper-edge of DIN-rail | 32.9 mm / 1.295 inches |
| Depth | 39.5 mm / 1.555 inches |
Mechanical data
| Mounting type | DIN-35 rail |
| Marking level | Center/side marking |
Environmental requirements
| Processing temperature | -35 … +85 °C |
| Continuous operating temperature | -60 … +105 °C |
Environmental Testing (Environmental Conditions)
| Test specification Railway applications – Rolling stock – Electronic equipment |
DIN EN 50155 (VDE 0115-200):2022-06 |
| Test procedure Railway applications – Rolling stock equipment – Shock and vibration tests |
DIN EN 61373 (VDE 0115-0106):2011-04 |
| Spectrum/Installation location | Service life test, Category 1, Class A/B |
| Function test with noise-like vibration | Test passed according to Section 8 of the standard |
| Frequency | f1 = 5 Hz to f2 = 150 Hz |
| Acceleration | 0.101g (highest test level used for all axes) |
| Test duration per axis | 10 min. |
| Test directions | X, Y and Z axes |
| Monitoring for contact faults/interruptions | Passed |
| Voltage drop measurement before and after each axis | Passed |
| Simulated service life test through increased levels of noise-like vibration | Test passed according to Section 9 of the standard |
| Frequency | f1 = 5 Hz to f2 = 150 Hz |
| Acceleration | 0.572g (highest test level used for all axes) |
| Test duration per axis | 5 h |
| Test directions | X, Y and Z axes |
| Extended test scope: Monitoring for contact faults/interruptions | Passed |
| Extended test scope: Voltage drop measurement before and after each axis | Passed |
| Shock test | Test passed according to Section 10 of the standard |
| Shock form | Half sine |
| Acceleration | 5g (highest test level used for all axes) |
| Shock duration | 30 ms |
| Number of shocks per axis | 3 pos. und 3 neg. |
| Test directions | X, Y and Z axes |
| Extended test scope: Monitoring for contact faults/interruptions | Passed |
| Extended test scope: Voltage drop measurement before and after each axis | Passed |
| Vibration and shock stress for rolling stock equipment | Passed |
2002-1201