4.9/5 - (866 bình chọn)
2-conductor through terminal block; 16 mm²; suitable for Ex e II applications; side and center marking; for DIN-rail 35 x 15 and 35 x 7.5; Push-in CAGE CLAMP®; 16,00 mm²; gray
2016-1201
Ex information
Reference hazardous areas | See application instructions in section “Knowledge and Downloads – Documentation – Additional Information: Technical Section; Technical Explications” |
Ratings per | ATEX: PTB 05 ATEX 1031 U / IECEx: PTB 05.0015U (Ex eb IIC Gb) |
Rated voltage EN (Ex e II) | 550V |
Rated current (Ex e II) | 70A |
Rated current (Ex e II) with jumper | 67A |
Power Loss
Power loss, per pole (potential) | 2.426W |
Rated current IN for specified power loss | 76A |
Resistance value for specified, current-dependent power loss | 0Ω |
Connection
Connection technology | Push-in CAGE CLAMP® |
Actuation type | Operating tool |
Connectable conductor materials | Copper |
Nominal cross-section | 16 mm² |
Solid conductor | 0.5 … 16 mm² / 20 … 6 AWG |
Solid conductor; push-in termination | 6 … 16 mm² / 14 … 6 AWG |
Fine-stranded conductor | 0.5 … 25 mm² / 20 … 4 AWG |
Fine-stranded conductor; with insulated ferrule | 0.5 … 16 mm² / 20 … 6 AWG |
Fine-stranded conductor; with ferrule; push-in termination | 6 … 16 mm² / 10 … 6 AWG |
Note (conductor cross-section) | Depending on the conductor characteristic, a conductor with a smaller cross-section can also be inserted via push-in termination. AWG specifications were converted according to IEC. |
Strip length | 18 … 20 mm / 0.71 … 0.79 inches |
Wiring direction | Front-entry wiring |
Physical data
Width | 12 mm / 0.472 inches |
Height | 69.8 mm / 2.748 inches |
Depth from upper-edge of DIN-rail | 36.9 mm / 1.453 inches |
Depth | 43.5 mm / 1.713 inches |
Environmental Testing (Environmental Conditions)
Test specification Railway applications – Rolling stock – Electronic equipment |
DIN EN 50155 (VDE 0115-200):2022-06 |
Test procedure Railway applications – Rolling stock equipment – Shock and vibration tests |
DIN EN 61373 (VDE 0115-0106):2011-04 |
Spectrum/Installation location | Service life test, Category 1, Class A/B |
Function test with noise-like vibration | Test passed according to Section 8 of the standard |
Frequency | f1 = 5 Hz to f2 = 150 Hz |
Acceleration | 0.101g (highest test level used for all axes) |
Test duration per axis | 10 min. |
Test directions | X, Y and Z axes |
Monitoring for contact faults/interruptions | Passed |
Voltage drop measurement before and after each axis | Passed |
Simulated service life test through increased levels of noise-like vibration | Test passed according to Section 9 of the standard |
Frequency | f1 = 5 Hz to f2 = 150 Hz |
Acceleration | 0.572g (highest test level used for all axes) |
Test duration per axis | 5 h |
Test directions | X, Y and Z axes |
Extended test scope: Monitoring for contact faults/interruptions | Passed |
Extended test scope: Voltage drop measurement before and after each axis | Passed |
Shock test | Test passed according to Section 10 of the standard |
Shock form | Half sine |
Acceleration | 5g (highest test level used for all axes) |
Shock duration | 30 ms |
Number of shocks per axis | 3 pos. und 3 neg. |
Test directions | X, Y and Z axes |
Extended test scope: Monitoring for contact faults/interruptions | Passed |
Extended test scope: Voltage drop measurement before and after each axis | Passed |
Vibration and shock stress for rolling stock equipment | Passed |