750-430
Number of digital inputs | 8 |
Total number of channels (module) | 8 |
Signal type | Digital |
Signal type (voltage) | 24 VDC |
Sensor connection | 8 x (1-wire) |
Input characteristic | high-side switching |
Input filter (digital) | 3ms |
Input current per channel for signal (1) typ. | 2.8mA |
Voltage range for signal (0) | −3 … +5 VDC |
Voltage range for signal (1) | 15 … 30 VDC |
Input data width (internal) max. | 8Bit |
Supply voltage (system) | 5 VDC; via data contacts |
Current consumption (5 V system supply) | 17mA |
Supply voltage (field) | 24 VDC (-25 … +30 %); via power jumper contacts (power supply via blade contact; transmission (supply voltage field side only) via spring contact) |
Isolation | 500 V system/field |
Indicators | LED (A-D) green: Status DI 1, DI 3, DI 5, DI 7; LED (E-H) green: Status DI 2, DI 4, DI 6, DI 8 |
Number of incoming power jumper contacts | 2 |
Number of outgoing power jumper contacts | 2 |
Current carrying capacity (power jumper contacts) | 10A |
Connection technology: inputs/outputs | 8 x CAGE CLAMP® (inputs) |
Connection type 1 | Input |
Solid conductor | 0.08 … 2.5 mm² / 28 … 14 AWG |
Fine-stranded conductor | 0.08 … 2.5 mm² / 28 … 14 AWG |
Strip length | 8 … 9 mm / 0.31 … 0.35 inches |
Width | 12 mm / 0.472 inches |
Height | 100 mm / 3.937 inches |
Depth | 67.8 mm / 2.669 inches |
Depth from upper-edge of DIN-rail | 60.6 mm / 2.386 inches |
Mounting type | DIN-35 rail |
Pluggable connector | fixed |
Color | light gray |
Housing material | Polycarbonate; polyamide 6.6 |
Fire load | 1.187MJ |
Weight | 47g |
Conformity marking | CE |
Ambient temperature (operation) | 0 … +55 °C |
Ambient temperature (storage) | -40 … +85 °C |
Protection type | IP20 |
Pollution degree | 2 per IEC 61131-2 |
Operating altitude | 0 … 2000 m / 0 … 6562 ft |
Mounting position | Horizontal left, horizontal right, horizontal up, horizontal down, vertical top and vertical bottom |
Relative humidity (without condensation) | 95% |
Vibration resistance | 4g per IEC 60068-2-6 |
Shock resistance | 15g per IEC 60068-2-27 |
EMC immunity to interference | per EN 61000-6-2, marine applications |
EMC emission of interference | per EN 61000-6-4, marine applications |
Exposure to pollutants | per IEC 60068-2-42 and IEC 60068-2-43 |
Permissible H2S contaminant concentration at a relative humidity 75 % | 10ppm |
Permissible SO2 contaminant concentration at a relative humidity 75 % | 25ppm |